Potencia de motor en
kW: 5.5 kW at 400/415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 9 kW
at 690 V AC 50/60 Hz 11 kW at 690 V AC 50/60 Hz
Poder de corte:
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at
690 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60
Hz conforming to IEC 60947-2 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC
60947-2 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC
60947-2
capacidad nominal de corte de cortocircuito de servicio: 100 %
at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz
conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC
60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at
440 V AC 50/60 Hz conforming to IEC 60947-2
Tipo de control:
pulsador.
corriente de disparo magnética: 170 A.
Tensión asignada
de empleo: 690 V AC 50/60 Hz conforming to IEC 60947-2.
Tensión
asignada de aislamiento: 690 V AC 50/60 Hz conforming to IEC
60947-2.
Intensidad térmica convencional: 14 A conforming to IEC
60947-4-1.
Tensión asignada de resitencia a los choques: 6 kV
conforme a IEC 60947-2.
Potencia total disipada por polo: 2,5
W
Endurancia mecánica: 100000 ciclos
Endurancia eléctrica: 100000
cycles for AC-3 at 440 V
Máximum operating rate: 25
cyc/h.
Servicio nominal: Continuous conforming to IEC
60947-4-1.